Partial Discharge Reference Guide

What is Partial Discharge?

Partial discharge (PD) is a localized electrical discharge that only partially bridges the insulation between conductors. It's an early indicator of insulation degradation in high-voltage equipment.

IEC 60270 Definition: "A localized electrical discharge that only partially bridges the insulation between conductors."

Example Severity Levels by Equipment

These levels are illustrative examples, not from a standard. IEC 60270 defines how to measure apparent charge in pC; it does not set severity limits. Acceptance levels come from the equipment standard or the manufacturer. For TEV, compare against background readings, against similar cells and against the trend over time.

Power Transformers (Oil-Filled)

PD Level (pC) Severity Action
<100NormalContinue monitoring
100-500LowIncrease monitoring
500-1,000ModerateInvestigate, DGA test
1,000-2,500HighPlan intervention
>2,500CriticalUrgent investigation

Switchgear (Metal-Clad)

TEV Level (dBmV) Severity Action
<-5NormalContinue monitoring
-5 to +5LowInvestigate next outage
+5 to +15ModerateSchedule investigation
+15 to +25HighPriority investigation
>+25CriticalUrgent action

PD Pattern Recognition

Pattern Phase Position Likely Defect
Near zero crossing0°, 180°Internal void
Near voltage peak90°, 270°Surface discharge
Negative half only180°-360°Corona (protrusion)
All phases, erraticRandomFloating electrode

Measurement Methods

Method Frequency Application
Conventional (IEC 60270)100 kHz - 1 MHzLab testing, commissioning
UHF300 MHz - 3 GHzGIS, transformers
Ultrasonic (40 kHz)AcousticTransformers, switchgear
TEVSurfaceMetal-clad switchgear