Serial with a gateway
Untested- For whom
- The PLC or module only has RS-485 (Modbus RTU).
- What is added to the panel
- A gateway with RS-485 that reaches the internet.
- Status
- Untested.
How it would be done
- The PLC is the Modbus slave. A gateway polls it over RS-485 and sends the registers.
- Cellular gateway: the Teltonika TRB145 is the one with RS-485 (the TRB140 has Ethernet and no RS-485). It works as a Modbus RTU client (master). Its “Data to Server” takes Modbus as an input, with an add-on package installed from its Package Manager, and sends over HTTP with the TLS option, or over MQTT, as JSON, a custom format or a Lua script. It fits where the customer has no network.
- Or a device with Node-RED and a USB to RS-485 adapter: the Modbus node (node-red-contrib-modbus) reads, the IAES node sends.
- Teltonika straight to Wertek AI: possible on paper, with the Lua script format. Untested. The specific doubt: generating a unique identifier per reading and putting the time of the measurement, which the IAES envelope requires.
Rows of the tables that point here: Delta DVP (ES2, SS2) · LS Electric XGB · Kinco K2 · Schneider M221 · Schneider Zelio · Brainchild IO (IO-8AII, IO-8TC, IO-6RTD, IO-16DI…) · Advantech ADAM-4000
Brand by brand, per the manufacturer
| Brand and PLC | How it would be done |
|---|---|
| Siemens LOGO! | With the CIM communication module (RS-232, RS-485, RS-422). |
| Siemens S7-1200 | The CPU has no serial port: a CM 1241 module or a CB 1241 board (RS-485) adds it, as Modbus master or slave. |
| Allen-Bradley Micro800 | A serial port configured as Modbus RTU. |
| Finder OPTA | The versions with RS-485; the manufacturer publishes Modbus RTU tutorials. |
| Delta DVP (ES2, SS2) | Built-in RS-485; the catalogue gives master or slave, Modbus ASCII or RTU, for the SS2. Most of them have no Ethernet; the ES2-E and the SE do. |
| WAGO Compact Controller 100 | One RS-485 port with Modbus RTU. |
| Weidmüller u-control UC20-WL2000-IOT | The controller has no serial port: the UR20-1COM-232-485-422 module adds it, as Modbus RTU master (release notes). Done by us in the field, not a manufacturer statement: the registers are not read from Node-RED directly; a Modbus register map in the controller configuration ties them to tags, and the Node-RED of the controller uses those tags. |
| Kinco (K2, K5, K6) | K2: RS-485 ports with Modbus RTU, master or slave, per the manual. K6: two RS-485 ports, Modbus RTU or ASCII, master or slave, per its spec sheet. K5: unverified. |
| LS Electric XGB | RS-485 built into the CPU with Modbus RTU and ASCII; XBL-C41A modules for more ports. |
| Mitsubishi FX5U | Built-in RS-485 with Modbus RTU, master or slave. |
| Schneider M221 | Serial line with Modbus RTU. |
| AutomationDirect CLICK PLUS | It depends on the CPU. C2-03CPU: RS-485 built in. C2-01CPU: RS-232 only, so it needs a converter to RS-485. C2-02CPU: no serial port. |
| Unitronics UniStream | Modbus RTU through the RS-485 of the Modular CPU, or through a serial COM module ordered apart. The Built-in series lists Ethernet and USB, no serial port. |
| Schneider Zelio | With the SR3MBU01BD module (RS-485, Modbus), on the SR3 B…BD relays (24 V DC). |
| Eaton easyE4 | With the EASY-COM-RTU-M1 communication module. The base unit has Ethernet, so Modbus TCP is its natural route. |
Sources: Teltonika, gateway families (which model has RS-485 or Ethernet) · Teltonika, TRB145 (the gateway with RS-485) · Teltonika, TRB145 Data to Server · Siemens, Modbus RTU on the S7-1200 (entry 47756141) · Eaton easyE4, product cybersecurity guideline (MZ049001EN) · Schneider, Zelio Logic catalogue (January 2022) · Kinco K6, spec sheet (copy hosted by a distributor) · Weidmüller UC20-WL2000-IOT, release notes